VFD Pump and Fan Energy Savings Calculator (Affinity Laws)

For centrifugal pumps and fans, flow varies with speed, head with speed squared and power with speed cubed. A modest speed reduction therefore gives a large power reduction. This calculator estimates the saving against throttling and the payback of a drive.

Your numbers

kW

Electrical power at 100% speed and design flow.

80 %
90 % of full

A throttled pump uses somewhat less than full power at reduced flow. 85 to 95 is typical for centrifugal pumps.

%
h
per kWh

Your results

Energy saved per year
66,990
kWh.
Cost saved per year
$8,039
Average power, throttled constant speed
27
kW.
Average power, with VFD
15.8351
kW, from the cube law including drive losses.
Power saved
11.1649
Simple payback
13.4 months

The cube law holds when there is little static head. Systems with high static head save less. A measured system curve is needed for a firm business case.

Save results:

Average power (kW) vs operating speed

Sweeps Average operating speed with VFD from 40 to 100, holding your other inputs fixed.

Energy candidate shortlist

Optional: shortlist drive candidates from your equipment and run hour data.

Optional. The tool and every export work without this. No spam.

How to use it

Enter the electrical power at full flow, the average speed you expect the drive to run at and how much power the pump draws today when throttled. Add the drive efficiency, run hours, tariff and installed cost. The result is average power, energy and cost savings per year and simple payback. The chart compares the two power curves across speed so you can see where the drive pays off.

The affinity laws

The affinity laws state that Q2/Q1 = N2/N1, H2/H1 = (N2/N1) squared and P2/P1 = (N2/N1) cubed. Running at 80% speed needs only about 51% of the power, before drive losses. The model divides by drive efficiency to account for losses in the converter. Throttled constant speed does not follow the cube law, so the baseline is an input rather than a formula.

  • A 10% speed reduction gives roughly a 27% power reduction
  • Savings shrink if the system has high static head
  • Fixed-flow processes gain nothing from a drive

Common mistakes

Applying the cube law to positive displacement pumps, which behave nearly linearly, is a frequent mistake. Others are using nameplate rather than measured power, assuming the pump will run at an average speed it never actually reaches, and ignoring minimum speed limits for cooling and bearing lubrication. Log actual flow demand for a few weeks before sizing the business case.

  • Using nameplate kW instead of measured kW
  • Applying fan or pump laws to constant-torque loads
  • Ignoring harmonics and cable length for drives

Frequently Asked Questions

How much does a VFD save on a pump?

It depends on how much flow reduction you need and how much static head the system has. For variable-flow centrifugal pumps with low static head, savings of 20 to 50 percent of energy are commonly seen, but verify with measurements.

What is the cube law?

Power required by a centrifugal pump or fan varies with the cube of speed, so a reduction to 80% speed needs about 51% of full power in an ideal case.

Does it work for any pump?

No. The laws apply to centrifugal machines. Positive displacement pumps deliver flow proportional to speed and need near-linear power, so savings are much smaller.

What payback is reasonable?

Drives on large, long-running, variable-flow loads often pay back in under two years. Short run hours or constant-flow duties can push payback beyond acceptable limits.

Netray can pull equipment run hours and energy meter data from ERP and historian sources to build a ranked list of drive candidates.